Occupational Hygiene - Gas Detection

On this page


What is a gas detector? 

Back to top

A gas detector, or gas monitor, is a device used to detect the presence and concentration of hazardous gases in the air. These devices are essential for workplace safety, especially in confined spaces, areas with limited ventilation, or locations where hazardous gases or atmospheres may be present. 

Gas detectors can be portable or fixed. Portable gas detectors are often referred to as personal gas monitors. Fixed gas detectors are installed in a permanent location where hazardous atmospheric conditions may be possible. Both are designed to alert users to potentially dangerous conditions through visual, audible, and vibration alarms. 


What can gas detectors measure? 

Back to top

Gas detectors measure a variety of hazardous gases depending on their sensors. Some common measurements include the lower explosive limit, gas concentration in parts per million, and oxygen concentration. Personal gas monitors may also measure the time-weighted average exposure and short-term exposure. 

Note: The terms "combustible" and "flammable" are often used interchangeably when referring to gases that can ignite and burn in air. The Workplace Hazardous Information System (WHMIS) uses the term "flammable gases," but gas detection equipment often refers to "combustible gas" detectors or sensors. Both terms describe gases that pose a fire or explosion risk when mixed with air at certain concentrations.

Lower Explosive Limit (LEL): 

The lower explosive limit indicates the concentration of a combustible gas in the air and is expressed as a percentage of the lower explosive limit. For example, a reading of 10% LEL means the concentration is 1/10th the amount needed to reach the lower explosive limit. 

Gases must be within a specific range (between the lower explosive limit and the upper explosive limit (UEL)) to ignite. Each flammable gas has its own range. When the concentration is below the lower explosive limit, there is not enough of the flammable gas to ignite, and above the upper explosive limit, there is not enough oxygen to ignite the gas. 

A black and orange rectangular sign with white text

AI-generated content may be incorrect. 

For example, methane has a lower explosive limit (LEL) of 5% by volume and an upper explosive limit (UEL) of 15% by volume, meaning methane will only ignite if there is a concentration of 5% by volume of methane in the air, which would be 100% of the lower explosive limit. If the gas detector is set to alert the user at 10% LEL, the gas detector would alert the user when the concentration of methane in the air is 0.5% by volume in the air. This alert level provides a buffer for workers to evacuate and ventilate the area before gas levels reach the flammable range. 

Gas Concentration in parts per million (ppm): 

Parts per million is a unit used to measure the concentration of toxic gases in the air. It expresses the amount of gas present as the number of parts of that substance in one million parts of air.

Toxic gases can pose serious health risks even at very low concentrations. Gas detectors measure these substances in parts per million to allow for sensitive and accurate monitoring. Occupational exposure limits (OELs) set by organizations such as the American Conference of Governmental Industrial Hygienists (ACGIH) or by regulatory agencies are typically listed in ppm. 

The effects of toxic gas exposure depend on the concentration of the gas and the time of exposure. Gas detectors usually alert users when the concentrations approach or exceed the occupational exposure limits. Some workplaces may choose more conservative alarm levels, depending on the level of risk and work conditions. 

For example, 10 ppm of nitrogen dioxide (NO2) means there are 10 molecules of nitrogen dioxide in every one million molecules of air. This level is equivalent to 0.001% by volume. This concentration of nitrogen dioxide exceeds the occupational exposure limit of 0.2 ppm, which demonstrates how some gases have a very low limit and how hazardous they can be. 

Oxygen Concentration (% by volume):

Oxygen concentration in the air is measured as a percent by volume. Normal, breathable air contains approximately 20.9% by volume of oxygen. Maintaining this level is important for having safe breathing air and for preventing atmospheric hazards in the workplace.

Unlike flammable or toxic gases, oxygen deficiency (too little oxygen) or enrichment (too much oxygen) may not have visible signs. Some gases may displace oxygen, or, in the case of too much oxygen, may make flammable gases ignite more easily. 

Oxygen-deficient environments may result from: 

  • Displacement by other gases 
  • Rusting (oxidation) in confined spaces
  • Biological activity (such as fermentation)

Oxygen-enriched environments can result from: 

  • Leaks from oxygen cylinders or supply lines
  • Use of oxygen in welding, cutting, or medical applications

Gas detectors can alert users to low oxygen levels of 19.5% by volume or high oxygen levels of 23.5% by volume. 

Average and Short-term Exposure:

Personal or portable gas detectors may calculate and display:

  • Time-weighted average (TWA)*: The average concentration of a hazardous substance over an 8-hour workday and a 40-hour workweek. 
  • Short-term Exposure Limit (STEL)*: The maximum concentration workers can be exposed to for 15 minutes, no more than 4 times per shift with at least 60 minutes between exposures. 
  • Peak: The highest gas concentration detected during the monitoring period. 

*These threshold limit values are defined by the American Conference of Governmental Industrial Hygienists (ACGIH). For more information on exposure limits, please see our OSH Answers Fact Sheet, Occupational Hygiene – Occupational Exposure Limits. 

The gas detectors with toxic gas sensors continuously monitor the air and record the gas concentrations over time. The monitor then calculates the average exposure using the total amount of exposure and compares it to the exposure limits pre-set in the device. 

For example, if a worker is exposed to low levels of carbon monoxide (CO) throughout the day with occasional peaks, the detector will record each data point, average those values over the relevant time period, and activate the alarm if the average exposure exceeds the set thresholds. This function is helpful as toxic effects can result from cumulative exposure over the shift. 


When and where should atmospheric testing occur? 

Back to top

Atmospheric testing should occur whenever there is a risk of toxic gases, oxygen deficiency, or explosive atmospheres. Gas detectors, similar to the smoke and carbon monoxide detectors in your home, can alert users or others in the area of potentially dangerous conditions. They are required in many situations but are often associated with work in confined spaces.  

For confined spaces, atmospheric testing must be conducted before entry. It must also be conducted: 

  • Continuously while work is ongoing, especially if conditions could change or work could generate new hazards. 
  • After any interruption in the work, or if the space has been closed for a period of time. 
  • At multiple levels. Be sure to measure the top, middle, and bottom of the space to detect gases of varying densities. Different gases have different physical properties and may create layers in tanks or other areas with poor ventilation. 
    • For example, hydrogen sulfide is heavier than air and may settle in low areas. 

For general work situations, atmospheric testing may be required:

  • Whenever work is taking place in an area with poor ventilation, such as pits, tunnels, or crawl spaces.
  • Before performing hot work in environments where flammable gases may be present. 
  • When chemical use or storage may release vapours or gases. 
  • After spills, leaks, or other incidents to make sure the area is safe to re-enter. 
  • Before and during maintenance work in process areas or enclosed equipment. 
  • If a worker reports odours, discomfort, or symptoms related to indoor air quality. 
  • If the nature of the work generates toxic gases. 
  • Whenever there is a risk of encountering a toxic or flammable gas. 

What is the difference between a calibration and a functional “bump” test? 

Back to top

Gas detection devices should be maintained regularly. 

Depending on the manufacturer, there may be different instructions for use. Always verify the frequency of functional tests and calibrations with the manufacturer. 

  • Functional tests, or bump tests, are quick tests in which the detector is exposed to a known concentration of gas to confirm that the sensors and alarms are working properly. They do not check for measurement accuracy, only that the sensors are working. This test should be done before each use. 
  • Calibrations are a more thorough process in which the detector’s sensors are adjusted using a known calibration gas concentration. This calibration ensures the detector provides accurate readings. Manufacturers typically recommend a monthly calibration for personal gas detectors, but frequency can vary based on use, manufacturer guidelines, workplace procedures, and regulatory requirements. 

After the functional test or calibration, completing a “zero” in fresh air is generally recommended. Zeroing the gas detector in fresh air sets a baseline for the sensors, similar to taring a scale before weighing.


How do combustible gas sensors work? 

Back to top

Combustible gas sensors detect flammable gases such as methane, propane, or hydrogen. These sensors measure gases as a percentage of the lower explosive limit (% LEL). 

Typically, these sensors use catalytic bead technology. The sensor contains two small beads, one active and one reference, which are heated to a high temperature. When the flammable gas enters the sensor: 

  • The gas burns on the surface of the active bead.
  • This reaction releases heat and changes the bead’s electrical resistance.
  • The sensor compares the change to the reference bead and outputs a signal proportional to the gas concentration. 
  • The reading is expressed as a percentage of the lower explosive limit (% LEL) of a target gas.

It is important to note that catalytic bead sensors do not identify specific flammable gases. They only measure the total concentration of flammable gas present. Because of this non-specificity, the type of calibration gas used is critical to ensure accurate readings in the intended workplace environment. 

Workplaces should identify which flammable gas or gases are likely to be present and select a calibration gas that matches or is close to the response characteristics. If there are numerous flammable gases present, pentane is generally recommended as a calibration gas if measuring a variety of hydrocarbons. Pentane tends to give a more conservative response for heavier hydrocarbons such as gasoline vapours or solvents. The manufacturer will be able to provide more insights into the best calibration gas for your situation.

Calibrating the sensor with a gas that has different characteristics from the actual hazard could cause an over- or under-estimation of flammable gas present. In these situations, a correction factor may need to be applied to determine the true concentration of a flammable gas. 

Some gases require a higher temperature to ignite and may be less responsive on a catalytic sensor. Sensor poisoning may also occur if the sensor is exposed to different hazardous products, such as silicones or lubricants (such as WD-40), as it could cover the active bead and degrade sensor performance. 

Combustible gas sensors with catalytic beads need at least 10% by volume of oxygen to accurately determine concentration. In situations where low oxygen levels are expected, infrared (IR) LEL sensors may be more appropriate. These sensors detect gas by measuring how infrared light is absorbed by the hydrocarbon gas molecules. 


How do toxic gas sensors work? 

Back to top

Toxic gas sensors (electrochemical sensors) detect harmful gases like carbon monoxide (CO), hydrogen sulfide (H₂S), chlorine (Cl₂), or ammonia (NH₃).

These sensors work when a gas passes through a semipermeable membrane. This membrane helps keep the sensors free of debris or other grime. When the gas reaches the sensor, a chemical reaction occurs inside the sensor, producing a current. The strength of the current is proportional to the gas concentration. 

Sensors typically provide a 90-100% response in about two minutes, depending on the gas and sensor. It is very important to wait for an accurate reading before entering a confined space or other potentially hazardous environment. In areas where there is a high concentration of gas, the reaction will be much quicker and alert users to the dangerous conditions. Always follow workplace procedures when an alarm is activated. 

There are additional considerations when using a gas detector with a pump and other accessories for measuring inside a confined space. For example, for every foot of tubing or length of wand, you need to wait an additional amount of time to allow for the gas to travel through the tube. The manufacturer can provide additional information on sensor sensitivity and special considerations when using attachments. 

It is important to note that toxic gas sensors can be affected by cross-sensitivity. For example, a sensor for hydrogen sulfide (H₂S) might also respond to sulfur dioxide (SO₂) or other sulfur compounds. Always refer to the manufacturer's data on known interferences.


How do you know what sensors or detectors to use? 

Back to top

Selecting the right gas detector and sensors is critical for alerting workers to potentially hazardous atmospheres. No single detector can identify all gases, so choosing the correct type depends on your specific work environment, known or potential hazards, and how the device will be used. 

Always start with hazard identification and risk assessment. By identifying which gases are present or are likely to be present, you can assess the risk and know which sensors are required to alert users of the hazard. 

Consider: 

  • Mobile equipment in enclosed workspaces. Running diesel or gasoline-powered equipment can generate carbon monoxide and nitrogen oxides. Charging batteries may produce hydrogen gas. 
  • Stored chemicals. 
  • By-products from welding, cutting, or combustion. 
  • Biological hazards, such as hydrogen sulfide in wastewater. 
  • Gas displacement. 
  • Process by-products. 

Different work environments pose different hazards, and the detector must be suitable for the type of work. 

Consider: 

  • Confined spaces where oxygen levels or toxic gases may vary. 
  • Hot work in areas where explosive atmospheres could form.
  • Cold or humid conditions may impact sensor performance. 
  • Industrial settings with corrosive gases or particulates which may damage sensors or clog filter membranes. 
  • Work environment. If there is a risk of an explosive atmosphere, the detectors should be intrinsically safe. 

When selecting a detector, there are several different types that offer single-gas monitoring, multi-gas monitoring, and multi-gas monitoring with a pump. Single-gas monitors are ideal when a specific hazard is known, whereas multi-gas monitors are used when multiple hazards may be present or unknown. The multi-gas monitors may have up to 6 different gas sensors. 

Remember that some gases may interfere with the accuracy of certain sensors. The manufacturer can advise you on these cross-sensitivities. Always choose sensors that match your specific hazards and review technical data sheets for accuracy and limitations.


What do you do if an alarm on the gas detector is activated?

Back to top

When an alarm sounds:

  • Recognize the alarm type. Different alarm levels may indicate different hazards, such as low alarm, high alarm, STEL, TWA, or sensor fault.
  • Follow workplace procedures and regulatory requirements.
  • Response to a personal gas detector alarm may include: 
    • Leave the area and go to fresh air or upwind.
    • Ventilate the space if safe to do so.
    • Notify your supervisor.
    • Continue monitoring the area if required for re-entry.
  • Response to a fixed gas detector alarm may include: 
    • Do not enter the alarm area. 
    • Alert others and evacuate the area.
    • Go to fresh air or upwind. 
    • Notify your supervisor. 
    • Activate emergency response procedures, if required.
    • Continue monitoring the area.

Alarms are typically based on occupational exposure limits or more conservative levels set by the organization. It is important that all workers are trained to recognize alarms, including lights, sounds, and vibrations, and understand emergency procedures.


Are there any other considerations when using gas detectors?

Back to top

Yes. In addition to selecting the right type of detector for the hazards and properly calibrating the sensors, several other factors contribute to the safe and effective use of gas detection equipment. 

Consider:

  • Storage and maintenance: Follow the manufacturer's storage, handling, and maintenance instructions. Improper storage can degrade sensors or damage the device.
  • Sensor life span: Electrochemical sensors degrade over time and have a limited service life, typically 2-3 years. Functional tests and calibrations can help users know when the sensors degrade, and some monitors may display warnings.
  • Environmental factors: Humidity, temperature, and pressure can affect sensor performance. Dusty environments or other particulates may also accumulate on the filter membrane. 
  • Safe work procedures: Establish written procedures for using gas detectors in your workplace. These procedures should cover how to use, test, and respond to alarms.
  • Training: Workers must be trained to understand, operate, and respond to their gas detectors. Training should include interpreting display readings, recognizing alarms, performing functional tests and calibrations, and taking action in response to unsafe conditions. 
  • Monitoring and data collection: Many gas detectors can log exposure data, including time-weighted average exposures, short-term exposure limits, peak exposures, and alarm events. Data can be downloaded from the devices or automatically uploaded when the device is docked. This information can be used to track trends, investigate incidents, or demonstrate due diligence and compliance. 

  • Fact sheet first published: 2026-11-25
  • Fact sheet last revised: 2026-11-25